Running power to pond , got to get the cable and box in pond end
Thank you for contacting Prysmian Group Technical Support
Just to clarify, these armoured cables are not suitable for submersion, therefore we would not recommend using these cables within the pond itself. Such cables as H07RN-F are more suitable so long as you confirm that the actual cable supplied can be submerged.
Shoudl you be using our armoured cable to provide power to a junction box near the pond, then subsequently use H07RN-F type, then standard armoured outdoor glands can be used. Prysmian can offer their Bicon branded products but others are widely available.
Unfortunately we cannot offer comment on junction boxes themselves.
Thank you
kind Regards
Technical Support
Answered by: Nikki - Prysmian
Date published: 2019-10-05