Suitable for SWA cable?
Can these glands be used with Steel Wire Armoured cable that is terminated in a fully plastic enclosure such as the British General Electric IP68 Outdoor sockets? If so would the steel armouring need to be earthed?
Asked by: JimmyMercury1920
Thank you for inquiry. The Tower Male Comp Gland is not suitable SWA Cable. They only intended for use with round pvc or rubber cable.
Answered by: SchneiderElectric Support
Date published: 2020-11-13
Cable size
Can you recommend a product that fits a 20 mm hole and can accept a 16mm round cable?
Asked by: RonAW
Thank you for your inquiry. The cable diameter that the 20mm Tower Male Comp gland will take is 10 - 14mm.
Answered by: SchneiderElectric Support
Date published: 2020-12-14
I wish to fit these glands to a metal fixing by not using the supplied nut, but to tap a thread into the metal fixing and screwing the gland in directly, What size thread would I need to cut?
Asked by: CCTVwizard
Thank you for the enquiry Mounting Thread:- 9.0mm Long M20 x 1.5mm, Spanner Size:- 24mm
Locknut 8.5mm thick M20 x 1.5mm, Spanner Size:- 24mm
Answered by: SchneiderElectric Support
Date published: 2020-11-27