Suitable to supply a small workshop?
Looking to connect up a small workshop with 1x 32A ringmain (sockets), 1 x lighting circuit (4x 45W LED battens) and 1x 110V tool transfomer switched via a fused spur.
I have been given 10mm2 swa, length of run is 25mtrs.
Asked by: VRSMatty
Hi, Please find link to data sheet https://new.abb.com/products/2CMA101189R1000/wall-mounted-inlets-2pe-32a-200-250-v
The plug is rated at 32A 250V so as long as you do not exceed this the plug will be fine however the main issue that I can see is that you are using 10mm2 cable and the capacity of this plug is 2.5-6mm2
Answered by: Anonymous
Date published: 2021-02-05